A voltage channel is available through any cable types that contain the "V" code. Example: ACC-EXP-NV03 Voltage channels are designed to read analog signal outputs from pressure, level, environmental, process, industrial and other sensors and meters. The Wildeye voltage channel also makes available a "Switched Power Output" power source to power an attached sensor. The following voltage range and SPO combinations are available:
Select the appropriate accessory to attach to your meter or sensor.
|
|
For detail specifications on the Wildeye Voltage channel, jump to Voltage Channel Details
Wildeye M12 "Field Connect" Wiring
M12 Field Connects are available in 3 different sizes to suit the thickness of the cable coming from your meter/sensor:
ACC-CON-M12-5POS-M-3 - For meters/sensors with output cable thickness 3-5mm diameter
ACC-CON-M12-5POS-M-6 - For meters/sensors with output cable thickness 5-7mm diameter
ACC-CON-M12-5POS-M-8 - For meters/sensors with output cable thickness 8-10mm diameter
Wildeye M12 "Bare Wire" Cable Wiring
Order part ACC-CAB-M12-M-5 "M12 Bare Wire Cable" for connecting to meter/sensors with terminal block connections.
Standards Wildeye Pinouts: NV03, NV02, NV, NV2, NV3, NV4, NV5
Field Connect pinout for connecting to standard Wildeye cable options NV03, NV02, NV, NV2, NV3, NV4, and NV5. For a complete list of cable type pinouts click here.
Field Connect Wiring:
ACC-CAB-M12-M-5 Wiring:
Voltage Channel Details |
![]() |
Voltage channel inputs are designed to read from meter/sensors that are powered either from the switched power output source on the wildeye itself or from an external permanent power source.
Voltage channels on a wildeye are generally intended to read sensors that are both powered and read from the wildeye, therefore the sensor itself is powered from the wildeye SPO.
This creates a stand-alone system fully battery powered and isolated from other noise sources and from ground. Telemetry communications are entirely wireless through the Outposts cellular modem, and setup is performed entirely through the mobile install app or website.
Voltage range and SPO options are available in the following combinations:
- 0-5V range with 12V SPO (default)
- 0-5V range with 5V SPO
- 0-5V range with 3V SPO
- 0-10V range with 12V SPO
- +-10V range with 12V SPO
General Characteristics of the wildeye Voltage channel:
- 15K ohm input impedance.
- 16-bit resolution, with 1% accuracy.
- SPO fixed at 12V, 5V or 3V depending on option purchased.
- Tolerant to 9V permanent over-voltage applied to the voltage channel.
To ensure the attached voltage sensor is compatible with the wildeye, the SPO stabilization time must be set to ensure the sensor device has enough time to power up and stabilize it's output before it is sampled. The sensor device will then powered-down again.
The stabilization time for each 4-20mA channel is programmed through the website interface. See Calibrating 4-20mA Analogue Channel for more info.