McCrometer SPI Flow Meter
Flow Meter Summary
Manufacturer | McCrometer |
Models | SPI |
Type | Insertion Meter |
Pulse Interface |
|
Programming |
|
Battery Life Claimed |
|
Support Contact | |
Straight Pipe Requirement | 10D upstream and 5D downstream. |
Pipe Sizes Supported |
|
Technical Manual |
|
Site Assessment
Note straight pipe requirements
Note full pipe requirements
Pulse Output Connections
Meter Pulse Output Port
<insert p
Pulse Interface Details
Pulse Output Type:
Pulse Width:
Pulse Cable Options
There are <> options to connect the <> to the Wildeye:
a)
b)
Example Wildeye Plug types with "C" Channels:
MCCD Plug (C1 Channel)
Wildeye <> Cable
For McMag3000 units ordered prior to Nov-2017 (Green top), use Wildeye part: ACC-CAB-MCMAG3000
For McMag3000 unit ordered after Nov-2017 (White top), use Wildeye part:
These custom McMag3000 to Wildeye cables will plug directly into any standard wildeye plug with a "C" channel.
Refer to Wildeye plug types with "C" channels above.
<> Pulse Output Cable
Use OEM Parts for Pulse Connection
Series
Pulse Output Programming
Step 1.
Set the Out 1 to #1 IMP+
-> Go to Menu 6
-> Select Out 1
-> Select #1 IMP+
Step 2
Set PLS1 to 0.01 or 0.1 KGL (Kilo Gallons)
For pipes size 8in or less, set 0.01 KiloGallons per pulse. For 10in or greater, set 0.1 KiloGallons per pulse
Step 3
Set Tpls1 to 50 milliseconds
-> Go to Menu 2
-> Select Tpls1
-> Select Tpls1=ms 0050.00
Pls1
The pulse increment value and unit of measure for the pulse output 1. This option is only available when “out1” in
"Menu 6 - Outputs" (section 7.6) is set to “#1 IMP”.
Tools needed:
-
Steps:
T